6. OPERATING THE VARIOUS LADDER MONITOR SCREENS
6 - 4
MELSEC
GOT
(2) When the MELSEC-QnA ladder monitor is executed
[Operation procedure]
1) Touch the ladder monitor starting touch switch on the monitor
screen prepared by the user or touch the
LADDER MON.
on the
utility screen to start the ladder monitor function.
2) The key window is displayed. Set the network No./station No. of
the applicable PLC CPU with the following keys.
: Select the input area.
Alphanumeric
: Input the network No. and the station No.
AC
: Clear all input data to the applicable area.
DEL
: Clear one character at the cursor position.
: Define the input.
To the following page
3) The PLC read screen appears.
First, touch the
Set Up
key to display the setting window.
POINT
If ROM_BIOS is not installed, an error message is
displayed. Touch the
END
button and install the
ROM_BIOS (H version or later).
POINT
Designate the network No. and the station No. of the
applicable PLC CPU.
(For CC-Link system)
Network No. : 0
Station No. : 0 (mask station)
(For network system)
Network No. : 1 to 255 (self-loop)
Station No. : 1 to 64 (control station)
1 to 64 (normal station)