Mitsubishi Electronics GOT-A900 Stereo Equalizer User Manual


 
12. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN
12 - 42
MELSEC
GOT
12.16 A616AD module monitor
12.16.1 Operation monitor
1)
6)
4)
5)
2)
3)
7)
No. Contents of display
Buffer memory address to
reference (hexadecimal)
1)
The specified conversion enabled/disabled status of each channel is
displayed.
F
2)
The set status of the data format for each channel is displayed.
0: Data format 48-4047
1: Data format 2048-2047
4
3)
The current output value, a value between 0 to 4000 for the digital output
value of each channel, is displayed as a percentage ranging from 0 to 100%.
30 to 3F
4) The error code is displayed when an error occurs. 5
5) The set value of the sampling period is displayed. 3
6) The channels where direct access occurs are displayed. 0
7)
The current output value, a value between 0 to 4000 for the digital output
value for each channel where direct access occurs, is displayed as a
percentage ranging from 0 to 100%.
2