17. USING THE NETWORK MONITOR SCREENS
17 - 3
MELSEC
GOT
17.2 Detailed own station monitor
This section describes the structure of the monitor screen and the common operations
used when executing the detailed own station monitor.
17.2.1 Display contents and keys functions: acting as a MELSECNET/B or MELSECNET (II) master station
This section describes the detailed own station monitor screen and the function of on-
screen keys, all of which are displayed and used when the own station acts as the
master station on the MELSECNET/B or MELSECNET (II).
(1) Display contents
When the A985/97*/960GOT is used When the A95*GOT is used
1)
3)
2)
The display details are the same
as the ones on the A985/97*
/960GOT.
Touch
button to change the
display.
(Display example)
No. Section Contents of Display
1) TsSt’s Info
•
This Station’s #
Indicates the station number of the own station.
•
This Station’s: Indicates the category of the own station.
2) D-Link Info
•
Total of L-Sta:
Indicates the maximum number of the stations to be linked.
The maximum number is defined by common parameters.
3) LoopBK Info
•
FLoop:
Shows the status of the primary loop lines of the own station.
(Normal/NG)
•
RLoop:
Shows the status of the secondary loop lines of the own
station. (Normal/NG)
•
Floop Back Station:
Indicates the station number of a station that executes the
loopback along the primary loop.
•
Rloop Back Station:
Indicates the station number of a station that executes the
loopback along the secondary loop.
•
# of Loop Switching:
Indicates the cumulative number of times for which loops
have been switched.
(2) Key functions
The table below shows the function of keys that are used on the detailed own
station monitor screen.
Key Function
RET
Returns to the own station monitor screen.
END
Exits the detailed own station monitor screen and returns to the
previous monitor screen where the network monitor function was
executed.
Changes the details on the window.
(only for A95*GOT)