12. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN
12 - 91
MELSEC
GOT
12.23.8 Monitoring Speed/Position Control
1)
2)
3)
4)
5)
Buffer memory address
to reference (decimal)
No. Contents of display
Axis 1 Axis 2 Axis 3
1)
The address (amount of movement) for position control in
speed/position changing control is displayed.
814
815
914
915
1014
1015
2)
The changed value is displayed when the position control
address (amount of movement) in the speed control function is
changed in speed/position changing control.
1164
1165
1214
1215
1264
1265
3)
The ON/OFF status of the speed/position changing latch flag
(the flag indicating the control status) is displayed. (The status of
Bit 1 of the pertinent buffer memory is displayed.)
"
: Position control in progress
#
: Speed control in progress/positioning is in progress in
another control method or operation method (such as
jogging)
817 917 1017
4)
This displays whether control switching in response to an
external signal is effective or not in speed/position changing
control.
1 : Switching is permitted
0 : Switching is not permitted
1163 1213 1263
5)
The ON/OFF status flag during speed control (the flag indicating
the control status) is displayed. (The status of Bit 0 of the
pertinent buffer memory is displayed.)
"
: Speed control in progress
#
: Position control in progress/positioning is in progress in
another control method or operation method (such as
jogging)
817 917 1017