3. SPECIFICATIONS
3.1 General Specifications
*1 Do not use or store the GOT under pressures higher than the atmospheric pressure of altitude 0m (0ft.).
Failure to observe this instruction may cause a malfunction.
When the air inside the control panel is purged by pressurization, the surface sheet may be lifted by high pressure. As a result,
the touch panel may be difficult to press, and the sheet may be peeled off.
*2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical
power distribution network and the machinery within the premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*3 This index indicates the degree to which conductive pollution is generated in the environment where the equipment is used.
In pollution degree 2, only non-conductive pollution occurs but temporary conductivity may be produced due to condensation.
Item Specifications
Operating ambient
temperature
Display section
0 to 50
Other than
display section
0 to 55 (when horizontally installed), 0 to 50 (when vertically installed)
Storage ambient temperature
-20 to 60
Operating ambient humidity
10 to 90%, non-condensing (WBT: 39 )
Storage ambient humidity 10 to 90%, non-condensing
Vibration resistance
Conforms to
JIS B 3502 and
IEC 61131-2
Frequency Acceleration
Half-
amplitude
Sweep count
Under
intermittent
vibration
5 to 8.4Hz - 3.5mm 10 times each in
X, Y and Z
directions
8.4 to 150Hz
9.8m/s
2
-
Under
continuous
vibration
5 to 8.4Hz - 1.75mm
-
8.4 to 150Hz
4.9m/s
2
-
Shock resistance
Conforms to JIS B 3502, IEC 61131-2 (147 m/s
2
, 3 times each in X, Y and Z directions)
Operating atmosphere
Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of electro
conductive dust particles and must be no direct sunlight. (Same as for saving)
Operating altitude
*1
2000 m (6562 ft) max.
Installation location Inside control panel
Overvoltage category
*2
II or less
Pollution degree
*3
2 or less
Cooling method Self-cooling
Grounding
Class D grounding (100 or less), to be connected to the panel when grounding is not possible.