14 - 14
14. GOT SELF CHECK (DEBUG AND SELF CHECK)
14.2 Self Check
14.2.5 I/O check
I/O check function
The I/O check is a function which checks whether GOT and PLC can communicate with each other.
If I/O check ends normally, the communication interface and the connection cable hardware are normal.
To execute I/O check, the communication driver has to be installed in GOT in advance from GT Designer3.
Note that the GOT restarts when this function is performed.
For the details related to the installation of the communication driver, refer to the following.
GT Designer3 Version1 Screen Design Manual (Fundamentals)
(1) Communication drivers inapplicable to I/O check
When the following communication drivers are used, the I/O check cannot be executed.
Display operation of I/O Check
Connection type Communication driver
Connection to MITSUBISHI PLC Ethernet connection Ethernet(MELSEC), Q17nNC, CRnD-700
Connection to YASKAWA PLC YASKAWA GL/CP9200(SH/H)/CP9300MS, Ethernet (YASKAWA)
Connection to YOKOGAWA PLC YOKOGAWA FA500/FA-M3/STARDOM, Ethernet (YOKOGAWA)
Connection to ALLEN-BRADLEY PLC EtherNet/IP(AB)
Connection to SIEMENS PLC SIEMENS S7, SIEMENS S7-200, SIEMENS S7-300/400
Microcomputer connection Computer
Inverter connection FREQROL 500/700
MODBUS(R)/TCP connection MODBUS/TCP
Connection to Azbil control equipment Azbil SDC/DMC
Connection to RKC temperature controller RKC SR Mini HG (MODBUS)
Debug & self check
Self check
Tou ch
[Debug & self check]
Tou ch
[Self check]
Main menu
I/O check
Tou ch
[I/O check]
(
9.3 Utility Display)