Mitsubishi Electronics GOT1000 Stereo Equalizer User Manual


 
18. TROUBLESHOOTING
18.2 Error Message and System Alarm
18 - 19
17
MAINTENANCE AND
INSPECTION
18
TROUBLESHOOTING
APPENDICES
540
Auto repeat error. Confirm
system information.
Error occurred while executing the auto repeat function of the touch
switch object.
Confirm the following.
Confirm that the other system error has not occurred during auto
repeat.
Confirm that any error information is not stored in the system
information/GS during auto repeat.
570 Recipe device points too large.
The number of the set points of the recipe device exceeds the specified
range.
Put the number of the set points of the recipe device within the specified
range.
571
Capacity shortage of user
memory (RAM)
There is no empty area/space in D drive.
Format the D drive in the memory to secure free area.
581 Abnormal Advanced recipe file
Advanced Recipe cannot be executed for advanced recipe file with
incorrect contents. Delete the advanced recipe file from the SD card or
USB memory.
582
Cannot generate Advanced
recipe file.
Cannot generate advanced recipe file. Confirm the following and execute
recipe processing again.
Confirm whether the SD card or USB memory is installed.
Confirm whether the SD card access switch of the GOT is ON.
Confirm the available memory of the SD card or USB memory.
583
Unable to save device value to
Advanced recipe file.
Unable to save device value to advanced recipe file.
Confirm the write-protection of the SD card or USB memory.
Confirm whether the attribute of saving file is for reading only.
584 Advance recipe file save error
An error has occurred during the advanced recipe file writing.
Do not pull out the SD card or USB memory while the Advanced Recipe
is operating.
585 Advanced recipe file upload error
An error has occurred during the advanced recipe file reading.
Do not pull out the SD card or USB memory while the Advanced Recipe
is operating.
586
Specified Advanced recipe
number does not exist.
The advanced recipe of non-existing number is about to be executed.
Execute advanced recipe of existing number.
587
Specified record number does
not exist.
The advanced record of non-existing number is about to be executed.
Execute record of existing number.
588
Cannot save recipe data to read
only record.
Saving recipe is about to be executed to the record of which recipe device
value cannot be edited.
Make the recipe device value of the record editable with Advanced
Recipe Setting of GT Designer3 or specify the record of which recipe
device value can be edited.
589
Recipe device save error. Recipe
file does not exist.
Saving recipe is about to be executed to the advanced recipe setting that
is set for not using file.
Specify the advanced recipe setting that uses file.
590
Recipe device upload error.
Recipe device value does not
exist.
Loading recipe is about to be executed to the record of which recipe
device value is not set.
Specify the record of which recipe device value is set.
591
Advanced Recipe error. Check
recipe data.
The advanced recipe setting is not correct.
Confirm the advanced recipe setting of the project data and download it
to the GOT again.
595 Logging file error.
Logging file error.
When collecting data again, delete logging files and management files.
Error
code
Error message Action
Channel No.
storage