Emerson Series 3000 MVD Satellite Radio User Manual


 
60 Micro Motion
®
Series 3000 MVD Transmitters and Controllers
Configuring Inputs
Density factor
(1)
0.0000 g/cm3 per
PSI
The change in fluid density per PSI. Not all sensors or applications require a
pressure correction factor for density. For the value to be used, see the product
data sheet for your sensor, then reverse the sign of the value listed for
pressure effect for density (e.g., if the pressure effect is 0.000004 % per PSI,
enter a pressure correction factor of –0.000004 % per PSI).
Calibration
pressure
(1)
0.0000 PSI The pressure at which the flowmeter was calibrated (which therefore defines
the pressure at which there will be no effect on the calibration factor). Refer to
the calibration document shipped with your sensor. If the data is unavailable,
use 20 psi.
External
temperature
compensation
(2)
Disable Select Enable to enable external temperature compensation.
• Select Disable to disable external temperature compensation.
(1) Displayed only if Polling Variable is set to Pressure.
(2) Displayed only if Polling Variable is set to Temperature.
Table 7-17 External input parameters continued
Variable Default Description