Configuring Custody Transfer
Note: If a single discrete input is assigned to print both a transfer (OIML) ticket and a standard or
batch ticket, only the transfer (OIML) ticket will be printed. With the exception of ticket printing and
transfer reset, you can assign one or more actions to a single discrete input. All applicable assigned
actions will be performed. Other discrete input actions and assignments are listed and defined in
Table 7-14.
If you will use the batch reset function, you can press the
RESET button from the batch
process screen, or you can assign the batch reset function to a discrete input or discrete
event (see Section 11.7).
7. If desired, you can define an alarm log password that will be required for the user to access the
active alarm log, the alarm history, and the event log. To do this, refer to Figure 14-2 and:
a. Define the four button-presses that will be used for the alarm log password.
b. Enable the alarm log password.
Note: Once enabled, the alarm log password will be required to re-enter this menu and change or
disable the alarm log password.
8. [Measuring Instruments Directive (MID) compliance] Read and document the Field
Verification Zero (FVZ) value. To read FVZ, you must configure the process monitor to
display it. See Section 12.3.
Note: This is required only for systems that include a transmitter. If your custody transfer application
is running on a Model 3300 or Model 3350 controller, you do not have an FVZ value.
9. (Gas applications in Germany) Read and document the checksum values for the transmitter
and core processor firmware in your flowmeter.
Note: The checksum values may also be useful for MID test reports.
10. Set the security switch on your Series 3000 device. The security switch is a hardware switch.
Security does not take effect until the security switch is ON. Detailed instructions for the
different Series 3000 devices are provided in Section 14.6.
11. Contact an authorized agent for installation of the Weights and Measures seal. Detailed
instructions for the different Series 3000 devices are provided in Section 14.7.