Operation Mode – Batch
Example 1
Batch control configuration:
No. of Stages = 2
Configure Presets By = % of Target
Preset configuration:
Target = 100 liters
Open Primary = 0%
m (Open Secondary) = 30%
n (Close Primary) = 70%
Operator actions:
None (see the first sequence in Figure 18-5)
As a result:
At the beginning of the batch run, the primary valve opens and flow
starts.
When the flowmeter has measured 30 liters, the secondary valve
opens.
When the flowmeter has measured 70 liters, the primary valve
closes.
When the flowmeter has measured 100 liters, the secondary valve
closes.
Example 2
Batch control configuration:
No. of Stages = 2
Configure Presets By = % of Target
Preset configuration:
Target = 100 liters
Open Primary = 0%
m (Open Secondary) = 30%
n (Close Primary) = 70%
Operator actions:
STOP/RESUME occurred after 20 liters had been measured (20%
of target; x = 20%) (see the second sequence in Figure 18-5)
As a result:
At the beginning of the batch run, the primary valve opens and flow
starts.
When the flowmeter has measured 50 liters (30 + 20, or m + x), the
secondary valve opens.
When the flowmeter has measured 70 liters, the primary valve
closes.
When the flowmeter has measured 100 liters, the secondary valve
closes.