96 Chapter 2
Programming Fundamentals
Using the LAN to Control the Analyzer
Emulated GPIB
Address The emulated GPIB address (bus address) is assigned
to the device to be controlled using SICL LAN. The
emulated GPIB address is automatically set to be the
same as the current GPIB address. The instrument is
shipped with the emulated GPIB address set to 18.
The SICL LAN server uses the GPIB name, GPIB logical unit number,
and GPIB address configuration on the SICL LAN client to
communicate with the client. You must match these parameters exactly
(including case) when you set up the SICL LAN client and server.
Configuring Your Analyzer as a SICL LAN Server
After you have collected the required information from the SICL LAN
client, perform the following steps to set up your analyzer as a SICL
LAN server:
1. Identify the GPIB name.
Press
System, Config I/O, SICL Server, Emulated GPIB Name, and notice
that it is gpib7.
2. Notice that the
Emulated GPIB Logical Unit is set to 8.
3. Notice that the
Emulated GPIB Address is set the same as the GPIB
address.
Configuring Your PC as a SICL LAN Client
The descriptions here are based on Agilent’s VISA revision G.02.02,
model number 2094G. A copy of Agilent’s VISA can be found by
following these steps:
1. Access the following Agilent website:
http://www.agilent.com/find/hpvee.
2. Look under “Vee Support, Instrument Drivers.”
These descriptions assume a LAN connection between your computer
and network analyzer. They are not written for the GPIB to LAN
gateway.
1. Install VISA revision G.02.02 or higher.
2. Run I/O configuration.
3. Select LAN Client from the available interface types.
4. Press Configure.
5. Enter an interface name, such as lan1.
6. Enter a logical unit number, such as 7.
7. Select Okay.