Honeywell ST 3000 Satellite Radio User Manual


 
6/08 ST 3000 Release 300 and SFC Model STS103 User’s Manual 67
6.2 Overview, Continued
Configuration
decision summary,
continued
Figure 25 Flowchart — ST 3000 Pressure Transmitter Configuration, continued.
B
Do you know how
much damping time
is needed?
NO
YES
Determine appropriate damping time value for your
process. We suggest that you set the damping to the
largest value that is reasonable for your process.
Select desired damping time
value in seconds through the
SFC prompt DAMP.
See procedure in Table 23 for selection details.
Press [
DAMP] key and use [NEXT] or [PREV] key to select
stored damping time value through SFC prompt DAMP 1.
Do you know what
engineering units to
use for pressure
readings?
NO
YES
See Unit of Measurement in Table 24 for list of available
pre-programmed engineering units in the SFC.
Select desired pre-programmed
engineering units through SFC
prompt UNITS.
See procedure in Table 24 for selection details.
Call up a pressure value on the SFC display and repeatedly
press [
UNITS] key to select desired pre-programmed
engineering units through the SFC prompt UNITS 1.
A
Continued on next page