ST 3000 Release 300 and SFC Model STS103 User’s Manual 6/08
142
7.8 Pressure or Liquid Level Measurement with GP
Transmitter,
Continued
Procedure, continued
Table 43 Starting Up GP Transmitter for Pressure or Liquid Level Measurement With SFC,
continued
Step Press Key Read Display or Action Description
8
If SFC and Then…
milliammeter
readings…
are zero (4mA) go to Step 11.
are not zero go to Step 9.
(4mA) and Tee
-connector is
level with
transmitter
are not zero go to Step 10.
(4mA) and Tee
-connector is
above
transmitter
9
^
SHIFT
INPUT
J
OUT-
PUT
RESET
K
COR-
RECT
NON-VOL
ENTER
(Yes)
PTOUT 3Ø111P
FT–SHI
PTINP 3Ø111UT
FC WOSING
.
RK ..
PTINP 3Ø111UT
.8 5473PSI
PTINP 3Ø111UT
ZRO NPUTEI
?
PTINP 3Ø111UT
FC WOSING
.
RK ..
PTINP 3Ø111UT
ZROENPUTIED
PTINP 3Ø111UT
Ø29ØPSI
Initiate shift key selection.
Read applied input pressure.
Prompt asks if the applied input
pressure equals zero input. If it is
zero input, go to next keystroke. If it
is not, press [
CLR] key to exit
function and try again.
Zero input is set equal to applied
input pressure. Go to Step 11.
Continued on next page