9.5 Replacing Meter Body
Procedure
You can replace the complete meter body including process heads or
only the meter body on selected DP, GP and AP transmitters by using
the existing process head(s).
Use the procedure in Table 56 to install a meter body only.
Table 56 Replacing Meter Body Only
Step Action
1
Complete first 3 Steps in Table 55, as applicable, to remove PWA.
2
Use 4 mm size hex wrench to completely loosen set screw outside
housing.
Process Head
Process Head
Meter Body
Set Screw
3
Carefully turn complete meter body counterclockwise to unscrew it
from electronics housing.
4
Remove nuts from bolts that hold process head or heads to center
section. Remove process heads and bolts
Continued on next page