6/08 ST 3000 Release 300 and SFC Model STS103 User’s Manual 119
6.12 Configuring Smart Meter Using Pushbuttons, Continued
Setting Upper Display
Values,
continued
Table 36 Setting Upper Display Value for Smart Meter Display, continued
Step Action Meter Display
14
Press UPPER VALUE button to lock in
current settings as upper display value and
return to previous display. Upper display limit
setting is now complete.
ATTENTION
For CUSTOM unit in
transmitter with LINEAR output, you must set
both lower and upper display limits for values
to take effect. If you let either the lower or
upper display limit time out (after 30 seconds),
the meter discards both newly set values and
reverts back to the previously set values.
Display goes blank for a 1/2 second and
returns to display readout equal to 50%
output.
In this example, readout is 9, 990,000
CUSTOM unit for 50% display range of 0 to
19,990,000 CUSTOM for transmitter with
LINEAR output.
%
1000
ANALOG
UPPER
VALUE
UNITS
LOWER
VALUE
SET
VAR
SEL.
K
9990
• If you have not yet set the lower display limit value for CUSTOM unit in a transmitter configured for
LINEAR output mode, the meter automatically enters the lower display setting function after it
displays previously set value, if applicable. Go to Table 35, Step 3.
• If you have already set the lower display limit value, this completes the lower and upper display limits
setting function for CUSTOM unit in transmitter configured for LINEAR output mode. Meter returns to
normal operation as shown in example display below.
• If you have just set the upper display limit for Flow unit or CUSTOM unit in transmitter configured for
SQUARE ROOT output mode, this completes the limit setting function. Meter returns to normal
operation as shown in example display below.
Continued on next page