Honeywell ST 3000 Satellite Radio User Manual


 
ST 3000 Release 300 and SFC Model STS103 User’s Manual 6/08
130
7.4 Flow Measurement with DP Transmitter, Continued
Procedure, continued
Table 39 Starting Up DP Transmitter for Flow Measurement With SFC, continued
Step Press Key Read Display or Action Description
9
^
SHIFT
INPUT
J
OUT-
PUT
RESET
K
COR-
RECT
NON-VOL
ENTER
(Yes)
PTOUT 3Ø111P
FT–SHI
PTINP 3Ø111UT
FC WOSING
.
RK ..
PTINP 3Ø111UT
.9 351Ø
"
H2O_39F
PTINP 3Ø111UT
ZRO NPUTEI
?
PTINP 3Ø111UT
FC WOSING
.
RK ..
PTINP 3Ø111UT
ZROENPUTIED
PTINP 3Ø111UT
Ø42Ø
"
H2O_39F
Initiate shift key selection.
Read applied input pressure.
Prompt asks if the applied input
pressure equals zero input. If it is
zero input, go to next keystroke. If it
is not, press [
CLR] key to exit
function and try again.
Zero input is set equal to applied
input pressure.
10
Repeat Steps 6 to 8.
11
Close equalizer valve C.
12
Open valve B and LP block-off valve to
begin measuring process differential
pressure.
13
Take SFC and milliammeter readings to
check that output signal does
correspond to applied input pressure. If
readings don’t correspond, check that
transmitter has been installed correctly.
If applicable, blow down piping to be
sure no foreign matter is entrapped in it.
Check SFC and milliammeter readings
again. If readings are still not correct,
verify transmitter’s configuration data
and change its range setting if needed.
14
Remove SFC and milliammeter from
loop.