6/08 ST 3000 Release 300 and SFC Model STS103 User’s Manual 203
11.6 Interpreting Messages
Interpretation table
Most of the diagnostic messages that can be displayed on the SFC are
listed in alphabetical order in Table 67 along with a description and
suggested action to be taken.
Table 67 Diagnostic Message Interpretation Table
Message Possible Cause What to Do
PT 3011
RHA M LTURPO ACF
STA STU
Characterization PROM is not
functioning correctly.
Replace meter body.
#T 011P3
RESETRECCOR ST
STATUS
All calibration “CORRECTS” were
deleted and data was reset to
default values.
Recalibrate transmitter.
PT 3011
OLE I >ACRN <ESTC
OUT 1P
No temperature compensation
data exists for calculations
.
Effect will be minor degradation of
ambient temperature influence
specifications. Replace electronics
module (PWA).
PT 3011
OLE I >BCRN <ESTC
OUT 1P
Transmitter’s nonvolatile memory
fault.
Replace electronics module (PWA).
PT 3011
OLE I >CCRN <ESTC
OUT 1P
Transmitter’s random access
memory (RAM) fault.
Replace electronics module (PWA).
PT 3011
OLE I >DCRN <ESTC
OUT 1P
Transmitter’s programmable read
only memory (PROM) fault.
Replace electronics module (PWA).
TAG O
ND NRREA D
N.
UROE
Communications unsuccessful. Check loop wiring and SFC
connections. If error persists,
replace transmitter.
#
T 0 1 1 P 3
N C O R R E S S E X C S
S T A T U S
P A
SPAN correction factor is outside
acceptable limits. Could be that
transmitter was in output mode.
Check input pressure and be sure it
matches calibrated range value.
Check meter body. Do a URV
CORRECT procedure.
#
T 0 1 1 P 3
O C O R R E S S E X C Z
S T A T U S
E R
ZERO correction factor is outside
acceptable limits. Could be that
either INPUT was incorrect or
transmitter was in output mode
during a CORRECT procedure.
Check input pressure and be sure it
matches calibrated range value.
Check meter body. Do an LRV
CORRECT procedure.
TAG O
AI OLD CFE MM
N.
CHK
SFC failed a communications
diagnostic check. Could be an
SFC electronic problem or a faulty
or dead communication loop.
Check polarity and try again.
• Press [
STAT] and do any
corrective action required and try
again.
Check communication loop.
Replace SFC.
TAG O
HI LEORO
N.
/LTSV
Either there is too much
resistance in loop (open circuit),
voltage is too low, or both.
Check polarity, wiring, and power
supply. There must be 11 volts
minimum at transmitter to permit
operation. Check for defective or
misapplied capacitive or inductive
devices (I/Ps) on the loop wiring.
Continued on next page