6.8 Setting Range Values Using Local Adjustments,
Continued
Procedure, continued
Table 27 Setting Range Values Using Local Zero and Span
Adjustments, continued
Step Action
9
a. Press and hold SPAN button on Local Zero and Span assembly or
Local Smart Meter.
%
1000
9
.
9
%
0
UPPER
VALUE
UNITS
LOWER
VALUE
SET
VAR
SEL.
SPAN
ZERO
Press &
Hold
ANALOG
ATTENTION
The Local Smart Meter readings revert to the default
unit of percent (%) during this operation. If the error code Er0
appears on the display, you are working with a model STD110
transmitter that does not support the Local Zero and Span
adjustments. If the error code Er4 appears, you are trying to set a
SPAN value that is outside acceptable limits for your transmitter.
Readjust applied pressure to be within acceptable range limits and
repeat this procedure.
b. Press Increase σ button once to complete this function.
ATTENTION
The Local Smart Meter display goes blank for a 1/2
second and then returns reading 100%.
%
1000
1
.
0
%
0
UPPER
VALUE
UNITS
LOWER
VALUE
SET
VAR
SEL.
SPAN
ZERO
Press once
ANALOG
Display goes
blank for 1/2
second and
returns with
100% reading
0
c. Check that milliammeter reading equals 20 mA and release SPAN
button.
ATTENTION
If milliammeter reading doesn’t change, be sure you
are not working with a model STD110 transmitter that ignores local
adjustments. The Local Smart Meter readings return to the set
engineering units after you release the SPAN button.
Continued on next page