ST 3000 Release 300 and SFC Model STS103 User’s Manual 6/08
190
10.4 Calibrating Range with SFC, Continued
Procedure, continued
Table 58 Calibrating Measurement Range With SFC, continued
Step Press Key Read Display or Action Description
9
NON-VOL
ENTER
(Yes)
ORK NGCW .F.S.I
PTLRV 3Ø111
PTLRV 3Ø111
LRV TRRECO C DE
PTLRV 3Ø111
ØØØ
.
ØØ
"
H2O
_
39F
Calibrates LRV to reference input
pressure for zero calibration.
10
Adjust pressure source to apply
pressure equal to URV (100%)
11
URV
100%
F
PTUR V 3Ø111
ØØØ
.
2Ø
"
H2O
_
39F
Present URV setting. If displayed
value does not match applied
pressure, key in matching URV
value or adjust pressure accordingly
before you press [
CORRECT] key in
next step.
12
RESET
K
COR-
RECT
PTUR V
U
3
Ø
11
T
1
RRRECO VC?
Prompt asks if URV is to be
calibrated to applied reference
pressure. If it is to be calibrated, go
to next Step. If it isn’t, press [
CLR]
key and try again.
13
NON-VOL
ENTER
(Yes)
ORK NGCW .F.S.I
PTURV 3Ø111
PTUR V 3
Ø
111
UR V TRRECO C DE
PTUR V 3Ø111
ØØØ
.
2Ø
"
H2O
_
39F
Calibrates URV to reference input
pressure for span (100%)
calibration.
14
^
SHIFT
NON-VOL
ENTER
(Yes)
FT–SHI
PTUR V 3Ø111
ORK NGCW .F.S.I
PTURV 3Ø111
PTUR V 3Ø111
NO VO ATLNDATA ILE
LIN DP
.Y. .READ
Initiate shift key selection
Saves data in transmitter’s
nonvolatile memory. This takes
approximately 8 seconds.
Continued on next page