Honeywell ST 3000 Satellite Radio User Manual


 
6/08 ST 3000 Release 300 and SFC Model STS103 User’s Manual 167
8.6 Monitoring Local Smart Meter Display, Continued
Operation error codes,
continued
Table 52 Possible Smart Meter Error Codes, continued.
If error indication is . . . Then, it means
%
1000
Er
ANALOG
%
4
UPPER
VALUE
UNITS
LOWER
VALUE
SET
VAR
SEL.
You have tried to set a span value that is outside
acceptable limits for your transmitter.
%
1000
Er
ANALOG
%
5
UPPER
VALUE
UNITS
LOWER
VALUE
SET
VAR
SEL.
You have tried to invoke a Local Smart Meter set function
with the transmitter’s Write Protect jumper in its Read Only
position. You cannot make changes in the Local Smart
Meter settings when the transmitter’s configuration is write
protected.
Meter/transmitter
interaction
Cycling transmitter power OFF/ON will have no affect on meter
configuration. The meter digital readout will be in the previously set
engineering units and applicable upper and lower display limits will be
intact when transmitter power is restored. (See
ATTENTION
in
Section 6.8 when setting range values and configuring the meter
display.)
If you switch the transmitter mode from Analog to DE, the ANALOG
indicator on the meter will go out. If you switch from DE to Analog
mode, the ANALOG indicator will light.
If you reconfigure the transmitter output conformity from SQUARE
ROOT to LINEAR, the meter’s digital readout will automatically
revert to the default engineering unit of percent and the FLOW
indicator will go out when the change is downloaded to the
transmitter. Likewise, if you reconfigure the transmitter output
conformity from LINEAR to SQUARE ROOT, the meter’s digital
readout will automatically revert to the default engineering unit of
percent and the FLOW indicator will light when the change is
downloaded to the transmitter. In either case, you must reconfigure the
transmitter as outlined in Section 6.11 or 6.12 of this manual.