7.10 Pressure Measurement with AP Transmitter, Continued
Procedure,
continued
Table 44 Starting Up AP Transmitter for Pressure Measurement With SFC, continued
Step Press Key Read Display or Action Description
4
NON-VOL
ENTER
(Yes)
TA ON.G
SFC WORKING.. .
LIN AG NO.DP T
P T3Ø11
Confirm that “TRIPS” are secured
and establish communications with
sample transmitter PT 3011
5
^
SHIFT
INPUT
J
OUT-
PUT
PTOUT 3Ø111P
FT–SHI
PTINP 3Ø111UT
FC WOSING
.
RK ..
PTINP 3Ø111UT
Ø42Ø PSI
Initiate shift key selection.
Read applied input pressure which
should be zero.
6
INPUT
J
OUT-
PUT
PTOUT 3Ø111P
FC WOSING.RK ..
%
PTOUT 3Ø111P
ØØØ
Call up output for display.
Read 0% output on display for
corresponding input pressure. For
analog transmission, check that
milliammeter reading is 4 mA (0%)
output.
7
Take SFC and milliammeter readings to
check that output signal does
correspond to zero and full-scale
pressures. If readings don’t correspond,
check that transmitter has been installed
correctly. If applicable, blow down piping
to be sure no foreign matter is entrapped
in it. Check SFC and milliammeter
readings again. If readings are still not
correct, verify transmitter’s configuration
data and change its range setting if
needed.
8
Remove SFC and milliammeter from
loop.