Honeywell ST 3000 Satellite Radio User Manual


 
ST 3000 Release 300 and SFC Model STS103 User’s Manual 6/08
126
7.3 Running Analog Output Check, Continued
Procedure, continued
Table 38 Using Transmitter in Constant-Current Source Mode, continued
Step Press Key Read Display or Action Description
6
NON-VOL
ENTER
(Yes)
PTOUT 30111P#
FC WOSING.RK ..
PTOUT
%
30111
3
.ØØØ
P#
Output signal is set at 30% (8.8
mA/2.2 V). A “#” character appears
on right side of display to remind
you that transmitter is in its output
mode.
7
Check that receiving device indication is
at its 30% point. If applicable, check that
milliammeter reading is 8.8 mA or
voltmeter reading is 2.2 V across 250
ohm resistor.
If indication is inaccurate, check
calibration of receiving device.
8
Repeat Steps 5 and 6 to check
indications at these output percentages.
If output is … Then meter
reads…
0% 4.0mA/1.0V
25% 8.0mA/2V
50% 12.0mA/3V
60% 13.6mA/3.4V
80% 16.8mA/4.2V
100% 20.0mA/5.0V
Use transmitter output as a
calibration input source for
instruments in loop.
9
INPUT
J
OUT-
PUT
CLR
(NO)
PTOUT 30111P#
FC WOSING.RK ..
%Ø.ØØ
PTOUT 30111P#
1
PTOUT 30111P#
FC WOSING.RK ..
LIN DP
.Y. .READ
T 011P3
Exit constant-current source mode.
Check that # character disappears
from right side of display since
transmitter is no longer in output
mode.
Continued on next page