Honeywell ST 3000 Satellite Radio User Manual


 
ST 3000 Release 300 and SFC Model STS103 User’s Manual 6/08
90
6.8 Setting Range Values Using Local Adjustments,
Continued
Procedure, continued
Table 27 Setting Range Values Using Local Zero and Span
Adjustments, continued
Step Action
10
Wait 30 seconds so that changes have been copied to the
transmitter’s non-volatile memory.
11
Remove applied pressure and turn OFF transmitter power.
12
Replace end-cap on PWA side of electronics housing and tighten
lock.
13
Remove milliammeter from TEST terminals and replace end-cap and
tighten lock.
14
Turn ON transmitter power and check Local Smart Meter reading, if
applicable.
Figure 32 Typical Setup for Setting Range Values Using Local Zero and Span Adjustments.
+
-
Field
Terminals
-
S
I
G
N
A
L
+
+
-
T
E
S
T
Power
Supply
+
-
Receiver
ST 3000
250
Ω
STR3015
Milliammeter