5.2 Enable or disable operator actions from the
display
You can configure the transmitter to let the operator perform specific actions using the
display.
You can configure the following:
• Totalizer Start/Stop
• Totalizer Reset
• Acknowledge All Alarms
5.2.1 Enable or disable Totalizer Start/Stop from the display
Display (standard) OFF-LINE MAINT > OFF-LINE CONFG > DISPLAY > TOTALS STOP
Chinese-language
display
Offline Maintain > Configuration > Display > Start Totals
Offline Maintain > Configuration > Display > Stop Totals
ProLink II ProLink > Configuration > Display > Display Options > Display Start/Stop Totalizers
ProLink III Device Tools > Configuration > Totalizer Control Methods
Field Communicator Configure > Manual Setup > Display > Display Variable Menu Features > Start/Stop Totalizers
Overview
You can control whether or not the operator is able to start and stop totalizers and
inventories from the display.
Restrictions
• You cannot start and stop totalizers individually from the display. All totalizers are started or
stopped together.
• You cannot start or stop inventories separately from totalizers. When a totalizer is started or
stopped, the associated inventory is also started or stopped.
• If the petroleum measurement application is installed on your computer, the operator must
enter the off-line password to perform this function, even if the off-line password is not
enabled.
Procedure
1. Ensure that at least one totalizer is configured as a display variable.
2. Enable or disable Totalizer Reset as desired.
Option Description
Enabled Operators can start and stop totalizers and inventories from the display,
if at least one totalizer is configured as a display variable.
Configure device options and preferences
64 Micro Motion
®
Model 1700 Transmitters with Analog Outputs