Gas Standard Volume Flow Cutoff affects both the gas standard volume flow values reported
via outputs and the gas standard volume flow values used in other transmitter behavior
(e.g., events defined on gas standard volume flow).
AO Cutoff affects only flow values reported via the mA output.
Example: Cutoff interaction with AO Cutoff lower than Gas Standard Volume Flow Cutoff
Configuration:
mA Output Process Variable for the primary mA output: Gas Standard Volume Flow Rate
Frequency Output Process Variable: Gas Standard Volume Flow Rate
AO Cutoff for the primary mA output: 10 SLPM (standard liters per minute)
Gas Standard Volume Flow Cutoff: 15 SLPM
Result: If the gas standard volume flow rate drops below 15 SLPM, the volume flow will be
reported as 0, and 0 will be used in all internal processing.
Example: Cutoff interaction with AO Cutoff higher than Gas Standard Volume Flow Cutoff
Configuration:
mA Output Process Variable for the primary mA output: Gas Standard Volume Flow Rate
Frequency Output Process Variable: Gas Standard Volume Flow Rate
AO Cutoff for the primary mA output: 15 SLPM (standard liters per minute)
Gas Standard Volume Flow Cutoff: 10 SLPM
Result:
If the gas standard volume flow rate drops below 15 SLPM but not below 10 SLPM:
- The primary mA output will report zero flow.
- The frequency output will report the actual flow rate, and the actual flow rate will
be used in all internal processing.
If the gas standard volume flow rate drops below 10 SLPM, both outputs will report
zero flow, and 0 will be used in all internal processing.
4.4 Configure Flow Direction
Display (standard) Not available
Chinese-language
display
Not available
ProLink II ProLink > Configuration > Flow > Flow Direction
ProLink III Device Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > Flow > Flow Direction
Configure process measurement
38 Micro Motion
®
Model 1700 Transmitters with Analog Outputs