Milliamp output problems and recommended actions (continued)Table 10-6:
Problem Possible causes Recommended actions
Consistently incorrect
mA measurement
Loop problem
Output not trimmed correctly
Incorrect flow measurement unit config-
ured
Incorrect process variable configured
LRV and URV are not set correctly
Check the mA output trim. See
Section 10.13.
Verify that the measurement units are con-
figured correctly for your application.
Verify the process variable assigned to the
mA output.
Check the settings of Upper Range Value and
Lower Range Value. See Section 10.17.
mA output correct at
lower current, but in-
correct at higher cur-
rent
mA loop resistance may be set too high Verify that the mA output load resistance
is below maximum supported load (see
the installation manual for your transmit-
ter).
10.7 Frequency output problems
Frequency output problems and recommended actionsTable 10-7:
Problem Possible causes Recommended actions
No frequency output Stopped totalizer
Process condition below cutoff
Fault condition if fault action is set to in-
ternal zero or downscale
Slug flow
Flow in reverse direction from config-
ured flow direction parameter
Bad frequency receiving device
Output level not compatible with receiv-
ing device
Bad output circuit
Incorrect internal/external power con-
figuration
Incorrect pulse width configuration
Output not powered
Wiring problem
Verify that the process conditions are below
the low-flow cutoff. Reconfigure the low-flow
cutoff if necessary.
Check the Fault Action settings. See
Section 10.18.
Verify that the totalizers are not stopped. A
stopped totalizer will cause the frequency
output to be locked.
Check for slug flow. See Section 10.25.
Check flow direction. See Section 10.23.
Verify that the receiving device, and the wir-
ing between the transmitter and the receiv-
ing device.
Verify that the channel is wired and config-
ured as a frequency output.
Verify the power configuration for the fre-
quency output (internal vs. external).
Check the pulse width. See Section 10.20.
Perform a loop test. See Section 10.12.
Consistently incorrect
frequency measure-
ment
Output not scaled correctly
Incorrect flow measurement unit config-
ured
Check the frequency output scaling. See
Section 10.21.
Verify that the measurement units are con-
figured correctly for your application.
Erratic frequency out-
put
Radio frequency interference (RFI) from
environment
Check for radio frequency interference. See
Section 10.19.
Troubleshooting