Emerson Model 1700 Satellite Radio User Manual


 
If Micro Motion is not listed, or you do not see the required device description, use the
Field Communicator Easy Upgrade Utility to install the device description, or contact
Micro Motion.
Field Communicator menus and messages
Many of the menus in this manual start with the On-Line menu. Ensure that you are able to
navigate to the On-Line menu.
As you use the Field Communicator with a Micro Motion transmitter, you will see a number
of messages and notes. This manual does not document all of these messages and notes.
Important
The user is responsible for responding to messages and notes and complying with all safety
messages.
E.2 Connect with the Field Communicator
A connection from the Field Communicator to your transmitter allows you to read process
data, configure the transmitter, and perform maintenance and troubleshooting tasks.
You can connect the Field Communicator to the mA terminals on the transmitter, to any
point in a local HART loop, or to any point in a HART multidrop network.
CAUTION!
If the transmitter is in a hazardous area, do not connect the Field Communicator to the mA
terminals on the transmitter. This connection requires opening the wiring compartment, and
opening the wiring compartment in a hazardous area can cause an explosion.
Prerequisites
The following HART device description (DD) must be installed on the
Field Communicator: .
Procedure
1. To connect to the transmitter terminals:
a. Remove the cover from the wiring compartment.
b. Attach the leads from the Field Communicator to terminals 1 and 2 on the
transmitter and add resistance as required.
The Field Communicator must be connected across a resistance of 250–600 .
Tip
HART connections are not polarity-sensitive. It does not matter which lead you attach to
which terminal.
Using the Field Communicator with the transmitter
Configuration and Use Manual 303