Configuration and Use Manual 73
Using the Filling and Dosing Application
Optional Configuration Using the FillerFiller ConfigurationUsing the Transmitter Optional Configuration Using the FillerFiller ConfigurationUsing the Transmitter Optional Configuration Using the FillerFiller ConfigurationUsing the Transmitter Optional Configuration Using the FillerFiller ConfigurationUsing the Transmitter
Figure 8-4 Fill sequences: Two-stage discrete fill, Open Primary at 0%, Close Secondary first
0% 100%
Normal operation
Configured values
Open Primary: 0%
Open Secondary: m%
Close Secondary: n%
Legend
•Primary valve
Secondary valve
•Flow
n%
0% m% 100%
x% before Secondary Open
n%x% m+x%
0% m% 100%
x% after Secondary Open,
when m+x% < n%
n%x% m+x%
0% m% 100%
x% after Secondary Open,
when m+x% > n%
n%x%
m+x%
0% m%
x% after Secondary Close
n% x% 100%m+x%
m%
Valve behavior with PAUSE/RESUME at x%