Emerson Process Management 1500 Satellite Radio User Manual


 
Configuration and Use Manual 97
Troubleshooting
Measurement Performance DefaultsTroubleshootingCompensation
A028 Comm Problem Cycle power to the flowmeter.
The transmitter might need service or upgrading. Contact Micro Motion. See
Section 1.8.
A032
(2)
Meter
Verification/Outputs In
Fault
Meter verification in progress, with outputs set to fault. Allow the procedure to
complete. If desired, abort the procedure and restart with outputs set to last
measured value.
A100 mA 1 Saturated See Section 11.18.
A101 mA 1 Fixed Exit mA output trim. See Section 3.4.
Exit mA output loop test. See Section 3.3.
Check to see if the output has been fixed via digital communication.
A102 Drive Overrange/
Partially Full Tube
Excessive drive gain. See Section 11.23.3.
Check the sensor coils. See Section 11.25.
A103
(1)
Data Loss Possible Cycle power to the flowmeter.
View the entire current configuration to determine what data were lost.
Configure any settings with missing or incorrect data.
The transmitter might need service. Contact Micro Motion. See Section 1.8.
A104 Cal in Progress Allow the flowmeter to complete calibration.
A105 Slug Flow See Section 11.17.
A107 Power Reset No action required.
A108 Event 1 On Be advised of alarm condition.
If you believe the event has been triggered erroneously, verify the Event 1
settings. See Section 6.9.
A109 Event 2 On Be advised of alarm condition.
If you believe the event has been triggered erroneously, verify the Event 2
settings. See Section 6.9.
A112 Upgrade Software Contact Micro Motion to get a transmitter software upgrade. See Section 1.8.
Note that the device is still functional.
A118 DO1 Fixed Exit discrete output loop test. See Section 3.3.
A119 DO2 Fixed Exit discrete output loop test. See Section 3.3.
A131
(2)
Meter
Verification/Outputs at
Last Value
Meter verification in progress, with outputs set to last measured value. Allow
the procedure to complete. If desired, abort the procedure and restart with
outputs set to fault.
(1) Applies only to systems with the standard core processor.
(2) Applies only to systems with the enhanced core processor.
Table 11-4 Status alarms and remedies continued
Alarm
code ProLink II label Possible remedy