Emerson Process Management 1500 Satellite Radio User Manual


 
102 Micro Motion
®
Model 1500 Transmitters with the Filling and Dosing Application
Troubleshooting
If fill accuracy is unsatisfactory or has changed, or if fill variation is too great:
Implement overshoot compensation (if not already implemented).
If standard AOC calibration is implemented, repeat the AOC calibration.
If rolling AOC calibration is implemented, try increasing the AOC Window Length value.
Check for mechanical problems with the valve.
11.14 Diagnosing wiring problems
Use the procedures in this section to check the transmitter installation for wiring problems.
11.14.1 Checking the power supply wiring
To check the power supply wiring:
1. Verify that the correct external fuse is used. An incorrect fuse can limit current to the
transmitter and keep it from initializing.
2. Power down the transmitter.
3. Ensure that the power supply wires are connected to the correct terminals. Refer to
Appendix B for diagrams.
4. Verify that the power supply wires are making good contact, and are not clamped to the wire
insulation.
5. Use a voltmeter to test the voltage at the transmitter’s power supply terminals. Verify that it is
within the specified limits. For DC power, you may need to size the cable. Refer to
Appendix B for diagrams, and see your transmitter installation manual for power supply
requirements.
11.14.2 Checking the sensor-to-transmitter wiring
To check the sensor-to-transmitter wiring, verify that:
The transmitter is connected to the sensor according to the wiring information provided in
your transmitter installation manual. Refer to Appendix B for diagrams.
The wires are making good contact with the terminals.
If the wires are incorrectly connected:
1. Power down the transmitter.
2. Correct the wiring.
3. Restore power to the transmitter.
11.14.3 Checking grounding
The sensor and the transmitter must be grounded. If the core processor is installed as part of the
sensor, it is grounded automatically. If the core processor is installed separately, it must be grounded
separately. See your sensor and transmitter installation manuals for grounding requirements and
instructions.