Example: Damping interaction
Configuration:
• Flow Damping = 1 second
• mA Output Process Variable = Mass Flow Rate
• Added Damping = 2 seconds
Result: A change in the mass flow rate will be reflected in the mA output over a time period
that is greater than 3 seconds. The exact time period is calculated by the transmitter
according to internal algorithms which are not configurable.
6.1.5 Configure mA Output Fault Action and mA Output Fault
Level
Display
Not available
ProLink II ProLink > Configuration > Analog Output > Primary/Secondary Output > AO Fault Action
ProLink > Configuration > Analog Output > Primary Output > AO Fault Level
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output 1 > MA01 Fault Settings
Configure > Manual Setup > Inputs/Outputs > mA Output 2 > MA02 Fault Settings
Overview
mA Output Fault Action controls the behavior of the mA output if the transmitter encounters
an internal fault condition.
Note
For some faults only: If Last Measured Value Timeout is set to a non-zero value, the transmitter will not
implement the fault action until the timeout has elapsed.
Procedure
1. Set mA Output Fault Action to the desired value.
The default setting is Downscale.
2. If you set mA Output Fault Action to Upscale or Downscale, set mA Output Fault Level as
desired.
Integrate the meter with the control system
90 Micro Motion
®
9739 MVD Transmitters