Option Setup
A user-configured
static pressure val-
ue
a. Set Pressure Unit to the desired unit.
b. Set Compensation Pressure to the desired value.
Polling for pres-
sure
(9)
a. Ensure that the primary mA output has been wired to support
HART polling.
b. Choose Online > Configure > Manual Setup > Measurements > External
Pressure/Temperature > External Polling.
c. Set Poll Control to Poll As Primary Host or Poll as Secondary Host.
d. Choose an unused polling slot.
e. Set External Tag to the HART tag of the external pressure device.
f. Set Polled Variable to Pressure.
Tip
• Poll as Primary: No other HART masters will be on the network.
• Poll as Secondary: Other HART masters will be on the network.
The Field Communicator is not a HART master.
A value written by
digital communica-
tions
a. Set Pressure Unit to the desired unit.
b. Perform the necessary host programming and communications
setup to write pressure data to the transmitter at appropriate in-
tervals.
Postrequisites
If you are receiving pressure data over the mA input, ensure that the mA input is
configured for your application.
If you are using an external pressure value, verify the setup by choosing Service Tools >
Variables > External Variables and checking the value displayed for External Pressure.
4.9.3
Options for Pressure Measurement Unit
The transmitter provides a standard set of measurement units for Pressure Measurement Unit.
Different communications tools may use different labels for the units. In most
applications, Pressure Measurement Unit should be set to match the pressure measurement
unit used by the remote device.
Options for Pressure Measurement UnitTable 4-14:
Unit description
Label
Display ProLink II ProLink III Field Communica-
tor
Feet water @ 68 °F
FTH2O
Ft Water @ 68°F
Ft Water @ 68°F ftH2O
(9) Not available on all transmitters.
Configure process measurement
Configuration and Use Manual 63