Emerson 9739 Satellite Radio User Manual


 
Interaction of Frequency Output Maximum Pulse Width and Frequency
Output Polarity
Table 6-6:
Polarity Pulse width
Active High
Active Low
Procedure
Set Frequency Output Maximum Pulse Width as desired.
The default value is 277 milliseconds. You can set Frequency Output Maximum Pulse Width to
0 milliseconds or to a value between 0.5 milliseconds and 277.5 milliseconds. The
transmitter automatically adjusts the value to the nearest valid value.
Tip
Micro Motion recommends leaving Frequency Output Maximum Pulse Width at the default value. Contact
Micro Motion customer service before changing Frequency Output Maximum Pulse Width.
6.2.6
Configure Frequency Output Fault Action and Frequency
Output Fault Level
Display
Not available
ProLink II ProLink > Configuration > Frequency > Freq Fault Action
ProLink > Configuration > Frequency > Freq Fault Level
Field Communicator Configure > Manual Setup > Inputs/Outputs > Frequency Output > FO Fault Parameters > FO Fault
Action
Configure > Manual Setup > Inputs/Outputs > Frequency Output > FO Fault Parameters > FO Fault
Level
Overview
Frequency Output Fault Action controls the behavior of the frequency output if the transmitter
encounters an internal fault condition.
Note
For some faults only: If Last Measured Value Timeout is set to a non-zero value, the transmitter will not
implement the fault action until the timeout has elapsed.
Integrate the meter with the control system
96 Micro Motion
®
9739 MVD Transmitters