Option Description
Enabled (default)
Operators can use a single display command to acknowledge all alarms
at once.
Disabled
Operators cannot acknowledge all alarms at once, they must be ac-
knowledged individually.
5.3 Configure security for the display menus
Display OFF-LINE MAINT > OFF-LINE CONFG > DISPLAY > OFFLN
ProLink II ProLink > Configuration > Display > Display Options > Display Offline Menu
Field Communicator
Not available
Overview
You can control operator access to different sections of the display off-line menu. You can
also configure a password to control access.
Procedure
1. To control operator access to the maintenance section of the off-line menu, enable
or disable Off-Line Menu.
Option
Description
Enabled (de-
fault)
Operator can access the maintenance section of the off-line menu. This
access is required for configuration and calibration, but is not required to
view alarms or to access Smart Meter Verification (if applicable).
Disabled
Operator cannot access the maintenance section of the off-line menu.
2. To control operator access to the alarm menu, enable or disable Alarm Menu.
Option
Description
Enabled (default)
Operator can access the alarm menu. This access is required to view and
acknowledge alarms, but is not required for Smart Meter Verification (if
applicable), configuration, or calibration.
Disabled
Operator cannot access the alarm menu.
Note
The transmitter status LED changes color to indicate that there are active alarms, but does
not show specific alarms.
Configure device options and preferences
72 Micro Motion
®
9739 MVD Transmitters