Important
Whenever you change a discrete output parameter, verify all other discrete output parameters
before returning the flowmeter to service. In some situations, the transmitter automatically loads a
set of stored values, and these values may not be appropriate for your application.
6.3.1 Configure Discrete Output Power Source
Display OFF-LINE MAINT > OFF-LINE CONFG > IO > DO > POWER
ProLink II ProLink > Configuration > Discrete Output > Power Type
Field Communicator Configure > Manual Setup > Inputs/Outputs > Discrete Output > Power Source
Overview
Use Discrete Output Power Source to set the output power source for the discrete output. The
power configuration must match the wiring for the discrete output.
Procedure
Set Discrete Output Power Source as desired.
Option
Description
Internal
The output is powered by the transmitter
External
The output is powered by an external power source.
6.3.2 Configure Discrete Output Source
Display OFF-LINE MAINT > OFF-LINE CONFG > IO > DO > SRC
ProLink II ProLink > Configuration > Discrete Output > Discrete Output > DO Assignment
Field Communicator Configure > Manual Setup > Inputs/Outputs > Discrete Output > DO Assignment
Overview
Discrete Output Source controls which flowmeter condition or process condition is reported
via the discrete output.
Procedure
Set Discrete Output Source to the desired option.
The default setting for Discrete Output Source is Flow Direction.
Integrate the meter with the control system