Procedure
Set Frequency Output Process Variable as desired.
The default setting is Mass Flow Rate.
Options for Frequency Output Process Variable
The transmitter provides a basic set of options for Frequency Output Process Variable, plus
several application-specific options. Different communications tools may use different
labels for the options.
6.2.3 Configure Frequency Output Polarity
Display OFF-LINE MAINT > OFF-LINE CONFG > IO > FO > POLAR
ProLink II ProLink > Configuration > Frequency > Freq Output Polarity
Field Communicator Configure > Manual Setup > Inputs/Outputs > Frequency Output > FO Settings > FO Polarity
Overview
Frequency Output Polarity controls how the output indicates the ON (active) state. The default
value, Active High, is appropriate for most applications. Active Low may be required by
applications that use low-frequency signals.
Procedure
Set Frequency Output Polarity as desired.
The default setting is Active High.
Options for Frequency Output Polarity
Options for Frequency Output PolarityTable 6-5:
Polarity Reference voltage (OFF) Pulse voltage (ON)
Active High
0 As determined by power sup-
ply, pull-up resistor, and load
(see the installation manual for
your transmitter)
Active Low
As determined by power sup-
ply, pull-up resistor, and load
(see the installation manual for
your transmitter)
0
Integrate the meter with the control system
Configuration and Use Manual 93