Emerson 9739 Satellite Radio User Manual


 
Options for HART variables (continued)Table 6-14:
Process variable Primary Varia-
ble (PV)
Secondary
Variable (SV)
Third Variable
(TV)
Fourth Varia-
ble (QV )
CM net mass total
CM net mass inventory
CM net volume flow rate
CM net volume total
CM net volume inventory
CM concentration
CM Baume
Interaction of HART variables and transmitter outputs
The HART variables are automatically reported through specific transmitter outputs. They
may also be reported through HART burst mode, if enabled on your transmitter.
HART variables and transmitter outputsTable 6-15:
HART variable Reported via Comments
Primary Variable (PV) Primary mA output If one assignment is changed, the other is changed auto-
matically, and vice versa.
Secondary Variable (SV) Secondary mA output If one assignment is changed, the other is changed auto-
matically, and vice versa. If your transmitter is not config-
ured for a secondary mA output, the SV must be config-
ured directly, and the value of the SV is available only via
digital communications.
Tertiary Variable (TV) Frequency output If one assignment is changed, the other is changed auto-
matically, and vice versa.
Quaternary Variable (QV) Not associated with an out-
put
The QV must be configured directly, and the value of the
QV is available only via digital communications.
6.7.2 Configure HART/RS-485 communications
Display
Not available
ProLink II ProLink > Configuration > Device > Digital Comm Setting
Field Communicator Configure > Manual Setup > Inputs/Outputs > Communications > Setup RS-485 Port
Overview
HART/RS-485 communications parameters support HART communication with the
transmitter's RS-485 terminals.
Integrate the meter with the control system
116 Micro Motion
®
9739 MVD Transmitters