Status alarms and recommended actions (continued)Table 10-2:
Alarm code Description Cause Recommended actions
A113 mA Output 2 Saturated • Check process conditions. Actual conditions
may be outside of the normal conditions for
which the output is configured.
• Verify process conditions, checking especially
for air in the flow tubes, tubes not filled, for-
eign material in the tubes, or coating in the
tubes.
• Verify that the measurement units are config-
ured correctly for your application.
• Purge the flow tubes.
• Check the settings of Upper Range Value and
Lower Range Value. See Section 10.17.
A114 mA Output 2 Fixed • Check whether the output is in loop test
mode. If it is, unfix the output.
• Exit mA output trim, if applicable.
• Check whether the output has been set to a
constant value via digital communication.
A115 No External Input or
Polled Data
The HART polling con-
nection to an external
device has failed. No re-
sponse received from
polled device.
The mA input connec-
tion to an external de-
vice has failed. No re-
sponse received from
the external device.
• Verify the external device operation.
• Verify the wiring between the transmitter and
the external device.
• Verify the HART polling configuration.
• Verify the mA input configuration.
A116 Temperature Over-
range (Petroleum)
• Check your process conditions against the val-
ues reported by the flowmeter.
• Verify the configuration of the petroleum
measurement table type and temperature.
A117 Density Overrange (Pe-
troleum)
• Check your process conditions against the val-
ues reported by the flowmeter.
• Verify the configuration of the petroleum
measurement table type and density.
A118 Discrete Output 1 Fixed The discrete output has
been configured to
send a constant value.
• Check whether the output is in loop test
mode. If it is, unfix the output.
A120 Curve Fit Failure (Con-
centration)
• Verify the configuration of the concentration
measurement application.
A121 Extrapolation Alarm
(Concentration)
• Check your process conditions against the val-
ues reported by the flowmeter.
• Verify the configuration of the concentration
measurement application.
Troubleshooting
Configuration and Use Manual 165