6.1.1 Configure mA Output Process Variable
Display OFF-LINE MAINT > OFF-LINE CONFG > IO > AO 1 > SRC
OFF-LINE MAINT > OFF-LINE CONFG > IO > AO 2 > SRC
ProLink II ProLink > Configuration > Analog Output > Primary/Secondary Output > PV/SV Is
Field Communicator Configure > Manual Setup > Inputs/Outputs > mA Output 1 > Primary Variable
Configure > Manual Setup > Inputs/Outputs > mA Output 2 > Secondary Variable
Overview
Use mA Output Process Variable to select the variable that is reported over the mA output.
Prerequisites
If you plan to configure the output to report volume flow, ensure that you have set
Volume Flow Type as desired: Liquid or Gas Standard Volume.
If you plan to configure an output to report a concentration measurement process
variable, ensure that the concentration measurement application is configured so
that the desired variable is available.
If you are using the HART variables, be aware that changing the configuration of mA
Output Process Variable will change the configuration of the HART Primary Variable
(PV) and/or the HART Secondary Variable (SV).
Procedure
Set mA Output Process Variable as desired.
Default settings are as follows:
Primary mA output: Mass Flow Rate
Secondary mA output: Density
Options for mA Output Process Variable
The transmitter provides a basic set of options for mA Output Process Variable, plus several
application-specific options. Different communications tools may use different labels for
the options.
Options for mA Output Process VariableTable 6-1:
Process variables Label
Display ProLink II ProLink III Field Communicator
Standard
Mass flow rate
MFLOW Mass Flow Rate Mass Flow Rate Mass flo
Volume flow rate
VFLOW Volume Flow Rate Volume Flow Rate Vol flo