Special mode and process variable updatesTable 5-1:
Always polled and updated
Updated only when the petroleum
measurement application is disa-
bled Never updated
Mass flow
Volume flow
Gas standard volume flow
Density
Temperature
Drive gain
LPO amplitude
Status [contains Event 1 and Event
2 (basic events)]
Raw tube frequency
Mass total
Volume total
Gas standard volume total
Temperature-corrected volume
total
Temperature-corrected density
Temperature-corrected volume
flow
Batch-weighted average tempera-
ture
Batch-weighted average density
RPO amplitude
Board temperature
Core input voltage
Mass inventory
Volume inventory
Gas standard volume inventory
All other process variables and calibra-
tion data. They retain the values held
at the time you enabled Special mode.
5.5 Configure alarm handling
The alarm handling parameters control the transmitter’s response to process and device
conditions.
Alarm handling parameters include:
Fault Timeout
Status Alarm Severity
5.5.1
Configure Fault Timeout
Display
Not available
ProLink II ProLink > Configuration > Alarm > Alarm
Field Communicator Configure > Alert Setup > Alert Severity > Fault Timeout
Overview
Fault Timeout controls the delay before fault actions are performed.
Configure device options and preferences
Configuration and Use Manual 75