144 Micro Motion
®
Model 2400S Transmitters for DeviceNet
Device Profile
C.2 Analog Input Point Object (0x0A)
Table C-1 Analog Input Point Object (0x0A) – Instance 1 (mass flow)
Attrib
ID Name Data type Service Mem Description Comments
3 Value REAL Get V Current value of mass
flow process variable
Based on Attribute 8
4 Status BOOL Get V Point status 0 = Good
• 1 = Alarm state
8 Value data type USINT Get V Data type used to report
mass flow process
variable
• 1 = REAL
100 Process total REAL Get
Reset
(1)
(1) Service code 0x4B.
V Current value of mass
total
101 Inventory total REAL Get
Reset
(2)
(2) Service code 0x4C.
V Current value of mass
inventory
102 Value
engineering
units
UINT Set NV Mass flow measurement
unit
See Table 6-2 for unit
codes.
103 Total
engineering
units
UINT Get V Mass total and inventory
units
Transmitter
automatically
determines this based
on Attribute 102.
See Table C-12 for unit
codes.
104 Damping REAL Set NV Flow damping value Unit = seconds
• Applied to both mass
flow and liquid volume
flow
105 Cutoff REAL Set NV Value below which mass
flow will be reported as 0
106 Meter factor REAL Set NV A multiplier to the
calculated mass flow
107 Flow direction USINT Set NV Determines how flow
direction affects reported
flow rate and flow totals
• 0 = Forward only
• 1 = Reverse only
• 2 = Bidirectional
• 3 = Absolute value
• 4 = Negate/forward
only
• 5 = Negate/
bidirectional
108 Reset mass total USINT Set V Resets the mass total • 1 = Reset
109 Reset mass
inventory
USINT Set V Resets the mass
inventory
• 1 = Reset