Display variable Process variable assignment
Display Variable 10
None
Display Variable 11
None
Display Variable 12
None
Display Variable 13
None
Display Variable 14
None
Display Variable 15
None
Configure Display Variable 1 to track the primary mA output
Display OFF-LINE MAINT > OFF-LINE CONFG > DISPLY > VAR 1
ProLink II ProLink > Configuration > Display > Display Options > Display Variable 1 Selection
ProLink III Device Tools > Configuration > Transmitter Display > Display Security
Field Communicator
Not available
Overview
You can configure Display Variable 1 to track mA Output Process Variable for the primary mA
output. When tracking is enabled, you can control Display Variable 1 from the display menu.
Tip
This feature is the only way to configure a display variable from the display menus, and it applies only
to Display Variable 1.
Procedure
Configure Display Variable 1 to track the primary mA output.
Display Variable 1 will automatically be set to match mA Output Process Variable for the primary
mA output. If you change the configuration of mA Output Process Variable, Display Variable 1
will be updated automatically.
5.1.3 Configure the precision of variables shown on the
display
Display
Not available
ProLink II ProLink > Configuration > Display > Display Precision
ProLink III Device Tools > Configuration > Transmitter Display > Display Variables
Field Communicator Configure > Manual Setup > Display > Decimal Places
Configure device options and preferences