Emerson MMI-20019043 Satellite Radio User Manual


 
Option Description
Primary
Use this setting if no other host is on the network. The Field Communicator is not
a host.
12. Click Connect.
Need help? If an error message appears:
Verify the HART address of the transmitter.
Ensure that you have specified the correct COM port.
Check the physical connection between the PC and the transmitter.
Increase or decrease resistance.
Ensure that there is no conflict with another HART master.
C.2.4 Make a HART/RS-485 connection
You can connect directly to the RS-485 terminals on the transmitter or to any point on the
network.
CAUTION!
If the transmitter is in a hazardous area, do not connect directly to the transmitter terminals.
Connecting directly to the transmitter terminals requires opening the wiring compartment,
and opening the wiring compartment while the transmitter is powered up could cause an
explosion. To connect to the transmitter in a hazardous environment, use a connection
method that does not require opening the wiring compartment.
Prerequisites
ProLink III installed and licensed on your PC
One of the following:
- RS-232 to RS-485 signal converter
- USB to RS-485 signal converter
An available serial port or USB port
Adapters as required (for example, 9-pin to 25-pin)
Procedure
1.
Attach the signal converter to the serial port or USB port on your PC.
2. To connect directly to the transmitter terminals:
a. Remove the transmitter end-cap to access the wiring compartment.
b. Connect the leads from the signal converter to terminals 5 (RS-485/A) and 6
(RS-485/B).
Using ProLink III with the transmitter
Configuration and Use Manual 305