Emerson MMI-20019043 Satellite Radio User Manual


 
- The frequency output will report the actual flow rate, and the actual flow rate will
be used in all internal processing.
If the mass flow rate drops below 10 g/sec, both outputs will report zero flow, and 0
will be used in all internal processing.
4.2 Configure volume flow measurement for liquid
applications
The volume flow measurement parameters control how liquid volume flow is measured
and reported.
The volume flow measurement parameters include:
Volume Flow Type
Volume Flow Measurement Unit
Volume Flow Cutoff
Restriction
You cannot implement both liquid volume flow and gas standard volume flow at the same time. You
must choose one or the other.
4.2.1 Configure Volume Flow Type for liquid applications
Display
Not available
ProLink II ProLink > Configuration > Flow > Vol Flow Type > Liquid Volume
ProLink III Device Tools > Configuration > Process Measurement > Flow
Field Communicator Configure > Manual Setup > Measurements > GSV > Volume Flow Type > Liquid
Overview
Volume Flow Type controls whether liquid or gas standard volume flow measurement will be
used.
Restriction
If you are using the petroleum measurement application, you must set Volume Flow Type to Liquid. Gas
standard volume measurement is incompatible with the petroleum measurement application.
Restriction
If you are using the concentration measurement application, you must set Volume Flow Type to Liquid.
Gas standard volume measurement is incompatible with the concentration measurement
application.
Configure process measurement
Configuration and Use Manual 29