4.6.1 Configure Temperature Measurement Unit
Display OFF-LINE MAINT > OFF-LINE CONFG > UNITS > TEMP
ProLink II ProLink > Configuration > Temperature > Temp Units
ProLink III Device Tools > Configuration > Process Measurement > Temperature
Field Communicator Configure > Manual Setup > Measurements > Temperature > Temperature Unit
Overview
Temperature Measurement Unit specifies the unit that will be used for temperature
measurement.
Procedure
Set Temperature Measurement Unit to the option you want to use.
The default setting is Degrees Celsius.
Options for Temperature Measurement Unit
The transmitter provides a standard set of units for Temperature Measurement Unit. Different
communications tools may use different labels for the units.
Options for Temperature Measurement UnitTable 4-12:
Unit description
Label
Display ProLink II ProLink III
Field Commu-
nicator
Degrees Celsius
°C degC °C degC
Degrees Fahrenheit
°F degF °F degF
Degrees Rankine
°R degR °R degR
Kelvin
°K degK °K Kelvin
4.6.2 Configure Temperature Damping
Display
Not available
ProLink II ProLink > Configuration > Temperature > Temp Damping
ProLink III Device Tools > Configuration > Temperature
Field Communicator Configure > Manual Setup > Measurements > Temperature > Temp Damping
Configure process measurement
Configuration and Use Manual 51