Honeywell SMV 3000 Satellite Radio User Manual


 
82 SMV 3000 Transmitter Users Manual 1/99
7.3 Running Output Check, Continued
Procedure, continued
Table 19 Analog Output Check Procedure, continued
Step Action
5
We assume that most analog transmitters will have PV4 as the
selected output. This also means that receiver instrument will be
configured to match PV4 output range.
If you have selected the analog output to represent another PV, be
sure it is the appropriate PV number used to check output.
6
Open the PV Monitor window by selecting PV Monitor from the View
pull down menu. Read the PV4 output.
7
Select FlowOutCal tab card and set output at 30% and place PV4 in
output mode.
8
Open PV Monitor window and read the PV4 in desired engineering
units that is equivalent to 30% output.
9
Verify 30% output on al receiver devices.
10
Select FlowOutCal tab card and clear the output mode of PV4.
11
Select Status tab card to verify that all transmitter outputs are in not in
output mode and that there are no new messages.
12
You can repeat steps 6 through 10 to simulate other PV outputs,
(such as PV1, PV2, or PV3).
Output Check
Procedure for SMV
Transmitters in DE
mode
The procedure in Table 20 outlines the steps for checking the PV outputs
for SMV transmitter in DE mode.
ATTENTION
The transmitter does not measure the given PV input or update the PV
output while it is in the output mode.
For SMV transmitters that are digitally integrated with Honeywells
TPS/TDC systems, note that PV readings on Universal Station displays
will be flagged as BAD PV although the PVRAW reading will continue
to be displayed will reflect the simulated input.
Continued on next page