Table 32 Non-Critical Status Diagnostic Message Table
SMV Status SCT Status Message SFC Display Message TDC Status Message Possible Cause What to Do
9-3 Bad AP Compensation
PV4
STATUS TAG ID.#
BAD AP COMP PV4
BAD AP COMP PV4
Problem with absolute/gauge
pressure input PV2 or input
processing circuitry for PV2.
Verify that absolute/gauge
pressure input is correct for
selected flow equation.
If error persists, replace
transmitter.
9-4 Bad PT Compensation
PV4
STATUS TAG ID.#
BAD PT COMP PV4
BAD PT COMP PV4
Problem with process temperature
input PV3, input processing circuitry
for PV3, or PV4 algorithm
parameter data.
Verify that process
temperature input is correct.
Verify open/defective
temperature sensor.
Correct process temperature
measurement.
Check for temperature limits
exceeded in viscosity or
density configuration.
Check design temperature
value for PV4 standard gas
algorithm.
2-6 Corrects Reset PV1
STATUS TAG ID.#
CORRECTS RST PV1
CORRECTS RST PV1
All calibration CORRECTS were
deleted and data was reset for PV1
range.
Recalibrate PV1 (DP) range.
4-6 Corrects Reset PV2
STATUS TAG ID.#
CORRECTS RST PV2
CORRECTS RST PV2
All calibration CORRECTS were
deleted and data was reset.
Recalibrate PV2 (SP) range.
8-6 Corrects Active on PV3
STATUS TAG ID.#
CORR. ACTIVE PV3
CORR. ACTIVE PV3
Process temperature PV3 has been
calibrated and is now different than
factory default (uncalibrated).
Nothing or do a reset corrects
Continued on next page