Honeywell SMV 3000 Satellite Radio User Manual


 
128 SMV 3000 Transmitter Users Manual 1/99
11.4 Diagnostic Messages, Continued
Diagnostic Messages,
continued
Table 32 Non-Critical Status Diagnostic Message Table, continued
SMV Status SCT Status Message SFC Display Message TDC Status Message Possible Cause What to Do
2-1
Excess Zero Correct
PV1
Or
Zero Correction is Out of
Limits
STATUS TAG ID.#
EX. ZERO COR PV1
EX. ZERO COR PV1
ZERO correction factor is outside
acceptable limits for PV1 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.
Verify calibration.
If error persists, call the
Solutions Support Center
4-1 Excess Zero Correct
PV2
STATUS TAG ID.#
EX. ZERO COR PV2
EX. ZERO COR PV2
ZERO correction factor is outside
acceptable limits for PV2 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.
Verify calibration.
If error persists, call the
Solutions Support Center
8-1 Excess Zero Correct
PV3
STATUS TAG ID.#
EX. ZERO COR PV3
EX. ZERO COR PV3
ZERO correction factor is outside
acceptable limits for PV3 range.
Verify calibration.
If error persists, call the
Solutions Support Center
9-1 Excess Zero Correct
PV4
STATUS TAG ID.#
EX. ZERO COR PV4
EX. ZERO COR PV4
ZERO correction factor is outside
acceptable limits for PV4 range.
Verify calibration.
If error persists, call the
Solutions Support Center
9-5 In Cutoff PV4
STATUS TAG ID.#
IN CUTOFF PV4
IN CUTOFF PV4
Calculated flow rate is within
configured low and high limits for
PV4 low flow cutoff.
Nothing wait for flow rate to
exceed configured high limit.
Verify that flow rate is in cutoff.
5-4 Input Mode PV1 (DP)
STATUS TAG ID.#
INPUT MODE PV1
INPUT MODE PV1
Transmitter is simulating input for
PV1.
Exit Input mode:
SCT Press Clear Input Mode
button on the DP InCal tab.
SFC Press [
SHIFT], [INPUT], and
[
CLR] keys.