Honeywell SMV 3000 Satellite Radio User Manual


 
1/99 SMV 3000 Transmitter Users Manual 163
A.5 Configuration, Continued
DAMPING Parameter
The damping value is a real number selection from the transmitter range
values shown in Table A-8 for a given SMV 3000 transmitter PV.
Table A-8 Damping Range Values for SMV 3000 Transmitter PVs
IF Process Variable Number is THEN Damping Value can be
PV1 or PV2
0.00, 0.16, 0.32, 0.48, 1.0, 2.0,
4.0, 8.0, 16.0, or 32.0 seconds
PV3
0.00, 0.3, 0.7, 1.5, 3.1, 6.3, 12.7, 25.5,
51.1, or 102.3 seconds
PV4
0.00, 0.5, 1.0, 2.0, 3.0, 4.0, 5.0, 10.0,
50.0, or 100.0 seconds
ATTENTION
The IOP may temporarily convert the entered damping value to a standard
damping enumeration until it accesses the transmitters database.
PIUOTDCF Parameter
This parameter represents the sensor fault detection ON/OFF selection for
PV3 only.
CJTACT Parameter
This parameter will apply for PV3 thermocouple input only. It defines
whether an internal cold-junction (ON) or an externally provided cold-
junction reference (OFF) is to be used.
After Point is Built
Once you complete the point build for PV1, you can start building the
point for the next PV or go to the Detail display for the point you just built
and either upload the transmitters database to the IOP or download the
IOPs transmitter database to the transmitter. See Section A-6 in this
Appendix and Section 7 in the PM/APM Smartline Transmitter
Integration Manual for operation data using the Universal Station.