6.8 TempConf Configuration - PV3, Continued
ATTENTION For a reverse range, enter the upper range value as the LRV and the
lower range value as the URV. For example, to make a 0 to 500 °F
range a reverse range, enter 500 as the LRV and 0 as the URV.
The URV changes automatically to compensate for any changes in the
LRV and maintain the present span (URV LRV). See Figure 23 for
an example.
If you must change both the LRV and URV, always change the LRV
first. However, if the change in the LRV would cause the URV to
exceed the URL, you would have to change the URV to narrow the
span before you could change the LRV
Figure 23 Example of LRV and URV Interaction
Current Range Settings
LRL LRV SPAN URV URL
-328 -100 257 600 842
o
F
Range Settings After LRV is Changed to Zero (0)
LRL LRV SPAN URV URL
-328 -100 0 257 600 700 842
o
F
Continued on next page